Sensor [SensorElementName] has transitioned to non-recoverable.
This message is for the use case when an implementation has detected a
Sensor transitioned to non-recoverable.
May also be shown as
800706080a01ffff or 0x800706080a01ffff
Alert Category
Critical - Power
CIM Information
Prefix:PLAT
and ID:0530
Automatically Notify Support
No
User Response
If the specified sensor is PS n 12V OC Fault, complete the following steps until the problem is solved:
- Use the IBM Power Configurator utility to determine current system power consumption. For more information and to download the utility, go to http://www-03.ibm.com/systems/bladecenter/resources/powerconfig.html.
- Follow actions in "Power Problems and Solving Power Problems".
If the specified sensor is PS n 12V OV Fault, complete the following steps until the problem is solved:
- Check power supply n LED.
- Remove the failing power supply.
- (Trained technician only) Replace the system board. (n = power supply number)
If the specified sensor is PS n 12V UV Fault, complete the following steps until the problem is solved:
- Check power supply n LED.
- Remove the failing power supply.
- Follow actions in "Power Problems and Solving Power Problems".
- (Trained technician only) Replace the system board. (n = power supply number)
If the specified sensor is PS n 12Vaux Fault, complete the following steps until the problem is solved:
- Check power supply n LED.
- Replace power supply n. (n = power supply number)