Explanation
Shutdown temperature threshold exceeded.
User Response
Inspect the enclosure and the enclosure environment.
- Check environmental temperature.
- Ensure that all of the components are installed or that there
are fillers in each bay.
- Check that all of the fans are installed and operating properly.
- Check for any obstructions to airflow, proper clearance for fresh inlet air, and exhaust air.
- Handle any specific obstructed airflow errors that are related
to the drive, the battery, and the power supply unit.
- Bring the system back online. If the system performed a hard shutdown,
the power must be removed and reapplied.
Possible Cause-FRUs or other:
Canister
(2%)
Battery (1%)
Power supply unit (1%)
Drive (1%)
Other:
Environment
(95%)