Explanation
The inter-canister
PCI Express link is operating with reduced capacity. This might be
a fault in either canister or the midplane. However, it is most likely
to be a fault in the node canister that reported the problem.
User Response
- Unless both nodes in the I/O group are online, fix the problem
that is causing the node to be offline first.
- Find which node reported the 1052 error by using the object_id or object_name value
for the event in the event log. Check which node canister has that node_id.
- Use the CLI command svctask rmnode to delete
the node canister that reported the problem.
- Replace the canister that reported the problem with the new canister.
- Wait for the new canister to be automatically added to the system.
- If the error is auto-fixed, then finish; otherwise, continue.
- Use the CLI command svctask rmnode to delete
the other node canister.
- Replace the other node canister with the old node canister.
- Wait for that node canister to be automatically added to the system.
- If the error is auto-fixed, then finish; otherwise, continue.
- Replace the enclosure.
- If the error is auto-fixed, then finish; otherwise, call IBM for
further support.
Possible Cause-FRUs
or other:
- Canister that reported the problem (50%)
- Other canister (30%)
- Enclosure (20%)